Registration Dossier
Registration Dossier
Data platform availability banner - registered substances factsheets
Please be aware that this old REACH registration data factsheet is no longer maintained; it remains frozen as of 19th May 2023.
The new ECHA CHEM database has been released by ECHA, and it now contains all REACH registration data. There are more details on the transition of ECHA's published data to ECHA CHEM here.
Diss Factsheets
Use of this information is subject to copyright laws and may require the permission of the owner of the information, as described in the ECHA Legal Notice.
EC number: 813-937-2 | CAS number: 111512-60-8
- Life Cycle description
- Uses advised against
- Endpoint summary
- Appearance / physical state / colour
- Melting point / freezing point
- Boiling point
- Density
- Particle size distribution (Granulometry)
- Vapour pressure
- Partition coefficient
- Water solubility
- Solubility in organic solvents / fat solubility
- Surface tension
- Flash point
- Auto flammability
- Flammability
- Explosiveness
- Oxidising properties
- Oxidation reduction potential
- Stability in organic solvents and identity of relevant degradation products
- Storage stability and reactivity towards container material
- Stability: thermal, sunlight, metals
- pH
- Dissociation constant
- Viscosity
- Additional physico-chemical information
- Additional physico-chemical properties of nanomaterials
- Nanomaterial agglomeration / aggregation
- Nanomaterial crystalline phase
- Nanomaterial crystallite and grain size
- Nanomaterial aspect ratio / shape
- Nanomaterial specific surface area
- Nanomaterial Zeta potential
- Nanomaterial surface chemistry
- Nanomaterial dustiness
- Nanomaterial porosity
- Nanomaterial pour density
- Nanomaterial photocatalytic activity
- Nanomaterial radical formation potential
- Nanomaterial catalytic activity
- Endpoint summary
- Stability
- Biodegradation
- Bioaccumulation
- Transport and distribution
- Environmental data
- Additional information on environmental fate and behaviour
- Ecotoxicological Summary
- Aquatic toxicity
- Endpoint summary
- Short-term toxicity to fish
- Long-term toxicity to fish
- Short-term toxicity to aquatic invertebrates
- Long-term toxicity to aquatic invertebrates
- Toxicity to aquatic algae and cyanobacteria
- Toxicity to aquatic plants other than algae
- Toxicity to microorganisms
- Endocrine disrupter testing in aquatic vertebrates – in vivo
- Toxicity to other aquatic organisms
- Sediment toxicity
- Terrestrial toxicity
- Biological effects monitoring
- Biotransformation and kinetics
- Additional ecotoxological information
- Toxicological Summary
- Toxicokinetics, metabolism and distribution
- Acute Toxicity
- Irritation / corrosion
- Sensitisation
- Repeated dose toxicity
- Genetic toxicity
- Carcinogenicity
- Toxicity to reproduction
- Specific investigations
- Exposure related observations in humans
- Toxic effects on livestock and pets
- Additional toxicological data
Flammability
Administrative data
Link to relevant study record(s)
- Endpoint:
- flammable gases
- Type of information:
- experimental study
- Adequacy of study:
- key study
- Study period:
- 19/02/2019 - 24/04/2019
- Reliability:
- 1 (reliable without restriction)
- Rationale for reliability incl. deficiencies:
- guideline study
- Qualifier:
- according to guideline
- Guideline:
- other: BS EN 1839:2009 (Method T)
- Deviations:
- not applicable
- GLP compliance:
- yes (incl. QA statement)
- Key result
- Parameter:
- lower explosion limit
- Remarks on result:
- no flammable range with air at 20°C and 101.3 kPa
- Remarks:
- At concentrations above 16%, sparking was suppressed by the mixture itself.
- Key result
- Parameter:
- upper explosion limit
- Remarks on result:
- no flammable range with air at 20°C and 101.3 kPa
- Remarks:
- At concentrations above 16%, sparking was suppressed by the mixture itself.
- Interpretation of results:
- not classified based on GHS criteria
- Conclusions:
- The test item HCFO-1224yd(Z) is not flammable.
- Executive summary:
A guideline A. 11 flammability study was performed on the test compound HCFO-1224yd(Z). The gaseous concentration was gradually increased from 1% to 19% of the test atmosphere. Below 16%, flame propagation did not occur, and above 16%, no sparks were observed (indicative of the test atmosphere becoming saturated and suppressing the spark). Consequently, HCFO-1224yd(Z) is determined not to meet CLP classification criteria for flammability.
- Endpoint:
- flammable gases
- Type of information:
- experimental study
- Adequacy of study:
- key study
- Study period:
- November 2016
- Reliability:
- 1 (reliable without restriction)
- Rationale for reliability incl. deficiencies:
- guideline study
- Qualifier:
- according to guideline
- Guideline:
- other: ASTM E681-2009
- Version / remarks:
- None
- Deviations:
- no
- Principles of method if other than guideline:
- Test method is based upon observation of flame propagation after electrical ignition, and is a standard method.
- GLP compliance:
- not specified
- Specific details on test material used for the study:
- Test substance was of 99.5% purity.
- Key result
- Parameter:
- lower explosion limit
- Value:
- >= 12 vol%
- Remarks on result:
- other: Not flammable
- Key result
- Parameter:
- upper explosion limit
- Value:
- >= 12 vol%
- Remarks on result:
- other: Not flammable
- Interpretation of results:
- GHS criteria not met
- Conclusions:
- Testing on HCFO-1224yd(Z) flammability has shown, by strict adherence to ASHRAE 34, that HC
FO-1224yd(Z) is non-flammable at 60°C. - Endpoint:
- flammable gases
- Type of information:
- experimental study
- Adequacy of study:
- key study
- Study period:
- 24/07/2017 - 17/08/2017
- Reliability:
- 1 (reliable without restriction)
- Rationale for reliability incl. deficiencies:
- guideline study
- Qualifier:
- according to guideline
- Guideline:
- EU Method A.11 (Flammability (Gases))
- Deviations:
- no
- GLP compliance:
- yes (incl. QA statement)
- Key result
- Parameter:
- lower explosion limit
- Value:
- >= 16 vol%
- Key result
- Parameter:
- upper explosion limit
- Value:
- <= 19 vol%
- Conclusions:
- The test material is considered flammable.
- Executive summary:
The test material is considered flammable with flammable range between 16 -19% volume.
HCFO 1224yd(Z) has been shown to be non-flammable at 60℃ using air at 50% relative humidity, 23℃ and 101.3 kPa, when tested according to ASTM E681-2009 and judged by ASHRAE Standard 34-2013.
Referenceopen allclose all
Description of key information
Key value for chemical safety assessment
- Flammability:
- not classified
Additional information
Justification for classification or non-classification
Introduction
The flammability of HCFO-1224yd(Z) has been assessed using three different testing procedures: ASTM E681-2009, BS EN 1876:2009 and EU Reg (EC) 440/2008, Annex Part A Test Method A.11. The substance performed differently in each study and, as such, a weight of evidence approach has been used to assess the data, as advised in paragraph R 7.1.10.1 of ECHA Guidance on Information Requirements and Chemical Safety Assessment Chapter R.7a: Endpoint specific guidance Version 6.0 – July 2017 (see below).
Weight of evidence
Where no single source of existing data (study reports, QSAR, literature data) is considered sufficiently reliable, thus not fully meeting the criteria in section 1.1.1 of Annex XI to REACH, or where several sources of similar reliability with deviating results exist, a weight of evidence approach may be used. The criteria in section 1.2 of Annex XI to REACH must then be met.
Test Results
1. ASTM E681-2009
HCFO-1224yd(Z) was tested for flammability according to ASTM E681-2009 and using the procedure required in ASHRAE Standard 34-2013. The test was conducted at 60oC, using air which had a humidity of 0.0088g water vapour/gm dry air, which equates to a relative humidity of 50% at 23oC and 101.3kPa. Flame propagation was determined as described in Appendix B1 of the ASHRAE Standard, which is the 90-degree fan criterion. HCFO-1224yd(Z) was tested at concentrations of 1.0% to 12.0% vol in air at increments of 1.0% and also at 9.5% (a total of 13 test runs). No flame propagation was observed at any concentration tested.
It was concluded that HCFO-1224yd(Z) was non-flammable at 60oC according to the criteria of ASHRAE Standard 34 and it was decided that it was not necessary to test the substance at 23oC.
2. BS EN 1876:2009
HCFO-1224yd(Z) was tested for flammability according to BS EN 1876:2009 (Method T).The method allows the determination of whether gases mixed with air at room temperature (circa 20°C) and atmospheric pressure are flammable. During the test, a spark is passed through the gas mixture and it is observed whether or not a flame occurs and detaches itself from the ignition source and propagates independently. If a flame detachment and an upwards propagation of at least 100 mm is observed, the test substance is classified as “Flammable”.
HCFO-1224yd(Z) was tested at concentrations of 1.0% to 19.0% vol in air at increments of 1.0% (a total of 19 test runs). A glow around the spark was observed at concentrations of HCFO-1224yd(Z) of 5.0 to 12.0%. A flame was observed when tested at concentrations of 13.0, 14.0 and 15.0%, but no detachment of the flame was observed. No flame was observed when tested at concentrations of 16.0% and above.
It was concluded that HCFO-1224yd(Z) was non-flammable according to the criteria of BS EN 1876:2009.
3. EU Reg (EC) 440/2008, Annex Part A Test Method A.11
HCFO-1224yd(Z) was tested for flammability in accordance withEU Reg (EC) 440/2008, Annex Part A Test Method A.11 (A.11 Test Protocol). The method allows the determination of whether gases mixed with air at room temperature (circa 20°C) and atmospheric pressure are flammable.The relevant data for the determination of whether the test substance is a non-flammable gas or a flammable gas is the occurrence of an independently propagated flame whena spark is passed through the gas mixture.
HCFO-1224yd(Z) was tested at concentrations of 1.0% to 10.0% vol in air at increments of 1.0%, at 12.0%, at concentrations of 14.0% to 20.0% at increments of 1.0%, at 22.0% and at 26.0% (a total of 27 test runs). A glow around the spark was observed at concentrations of HCFO-1224yd(Z) of 5.0 to 12.0%. An orange flame that did not propagate was observed when tested at concentrations of 15.0% and 20.0%. An orange flame that propagated no more than 70mm was observed when tested at concentrations of 16.0, 17.0, 18.0 and 19.0%. No flame was observed when tested at concentrations of 22.0% and above.
The criteria for the determination of the flammability of a gas at 20°C according to this method are as follows:
Category 1 Extremely Flammable Gas;
(a) ignitable when in a mixture of 13 % or less by volume in air; or
(b) have a flammable range with air of at least 12 percentage points regardless of the lower
flammable limit.
Category 2 Flammable Gas.
Gases, other than those of Category 1, which, at 20°C and a standard pressure of 101.3 kPa, have a flammable range while mixed in air.
Consequently, whilst it had a flammable range but did not ignite at concentrations of 13.0% or less, it was concluded that HCFO-1224yd(Z) would be classified as a Category 2 Flammable Gas according to the criteria ofEU Reg (EC) 440/2008, Annex Part A Test Method A.11.
It should be noted that this test, as conducted, also complied with test method BS EN 1876:2009. As the flame was not propagated further than 100 mm at any of the concentrations tested, the results of this study would indicate thatHCFO-1224yd(Z) would be classified as a non-flammable according to the criteria of BS EN 1876:2009.
Discussion.
Three flammability studies have been performed with HCFO-1224yd(Z) according to different test protocols, two of which found the test substance to be non-flammable and a third which showed it to be flammable.
The studies conducted according to bothBS EN 1876:2009 andEU Reg (EC) 440/2008, Annex Part A Test Method A.11were conducted at the same facility (DEKRA Chilworth Laboratory) using the same test apparatus, yet they provided different results. Both tests were conducted to GLP and were conducted on 28/29.03.19 andbetween 24.07.17 and 17.08.17respectively. Possible reasons for these differences have been considered and discussed with the facility, where appropriate.
1. Test Substance.
The samples of test substance for both studies were supplied by the manufacturer, Asahi Glass Co. Ltd., from their Chiba plant in Japan.
The Certificate of Analysis (CoA) for the sample submitted for the study conducted to the A.11 test protocol showed that the sample was 99.444%(Z)-1-Chloro-2,3,3,3-tetrafluoropropene, with its cis-trans isomer, (E)-1-Chloro-2,3,3,3-tetrafluoropropene, being declared as an impurity and being present at 0.341%.
The Certificate of Analysis (CoA) for the sample submitted for the study conducted to BS EN 1876:2009 showed that the sample was 99.48%(Z)-1-Chloro-2,3,3,3-tetrafluoropropene, with its cis-trans isomer, (E)-1-Chloro-2,3,3,3-tetrafluoropropene, being declared as an impurity and being present at 0.47%.
The report of the test conducted to ASTM E681-2009 does not include a CoA. However, the following statement is included in the report – “There are no contaminants or impurities, including isomeric and decomposition impurities, from manufacturing, transport or storage that are known to increase flammability or toxicity of the blend within the accuracy of the RCL.” (The definition of RCL is unknown.)
Taking all of this information into account, it is unlikely that the small differences in the levels of impurity in the two samples tested by DEKRA would explain the difference in performance of the samples in the two studies.
2. Experimental Equipment.
The study protocols provided by the laboratory for both studies described a number of variables that may have an impact on the level of energy input to the system; e.g. distance between the two electrodes (the protocol states that this can vary between 3 and 5 mm; output voltage (the protocol states that this can vary between 10 and 15 kV); duration of spark (the protocol states that the spark is offered for 0.5 seconds).
DEKRA have stated that there were no changes or modifications to the experimental apparatus that was used to perform the two studies and that variability in the spark time would not have occurred, as itis controlled by a relay and therefore should be unchanged.
It is concluded that changes to the experimental equipment would not have contributed to the difference in performance of HCFO-1224yd(Z) in the two studies.
There are significant differences in the design of the test apparatus used in both the BS EN 1876:2009 andthe A.11 Test Protocol and that used in ASTM E681-2009 and the protocols that are used. The two former test systems employ a cylindrical vessel, into which the test gas is introduced at the bottom. The ASTM method employs a spherical flask which eliminates “wall effect” issues and increase the likelihood of full homogenisation of the test gas in the vessel. Furthermore, the humidity in the ASTM test system is controlled, the criteria for ignition is more robust and the temperature of the test atmosphere can be monitored. These differences lead to a greater degree of confidence in the results of the ASTM test protocol.
3. Ambient Conditions.
It is possible that differences in the ambient conditions (barometric pressure, humidity and temperature) may have contributed to the difference in performance of HCFO-1224yd(Z) in the two studies.
| 2017 | 2019 |
DATES | 24thJuly to 9thAugust | 28thand 29thMarch |
Barometric Pressure | Ranged between 100.8 kPa and 101.7 kPa | 103.6 kPa and 103.1 kPa |
Humidity | Ranged between 46% and 58% | 24% and 26% |
Temperature | 19 – 21°C | 19 – 21°C |
There was only a minimal difference in the barometric pressure at the times that the two studies were conducted. It is unlikely that this small difference would have contributed to the difference in performance of HCFO-1224yd(Z) in the studies.
There was a significant difference in the humidity at the times that the two studies were conducted. It would be reasonable to assume that substances would be more prone to ignite under conditions of lower humidity. As such, one might expect that the conditions of the test conducted in 2019 would have been more favourable to support an ignition. In fact, the opposite occurred; ignition of HCFO-1224yd(Z) was observed at a time when the humidity was high. Furthermore, moisture-free compressed gas is used to prepare the gas mixture that is introduced to the test apparatus. Consequently, the ambient humidity would have no impact on the performance of the tests. It is concluded that differences in humidity did not contribute to the difference in performance of HCFO-1224yd(Z) in the studies.
Conclusion
There are no clear factors in the conduct of the three studies that can explain the difference of performance of HCFO-1224yd(Z). It is generally known that halogenated compounds are difficult to ignite. In the experience of DEKRA, it is not uncommon for non-flammable compounds to show a flame upon initiation of the spark. Sometimes the flame propagates and sometimes it does not. This experimental variation appears to be the most likely explanation of the results of the studies conducted by DEKRA. Furthermore, critical differences in the conduct of the ASTM test lead to a greater degree of confidence in the results of the ASTM test protocol.
Taking all of these points into account, it is concluded that the weight of evidence supports the conclusion that HCFO-1224yd(Z) is Not Flammable.
Information on Registered Substances comes from registration dossiers which have been assigned a registration number. The assignment of a registration number does however not guarantee that the information in the dossier is correct or that the dossier is compliant with Regulation (EC) No 1907/2006 (the REACH Regulation). This information has not been reviewed or verified by the Agency or any other authority. The content is subject to change without prior notice.
Reproduction or further distribution of this information may be subject to copyright protection. Use of the information without obtaining the permission from the owner(s) of the respective information might violate the rights of the owner.