Physical & Chemical properties

Flash point

Currently viewing:

Administrative data

Link to relevant study record(s)

Reference
Endpoint:
flash point, other
Type of information:
experimental study
Adequacy of study:
key study
Study period:
2017
Reliability:
1 (reliable without restriction)
Rationale for reliability incl. deficiencies:
guideline study
Qualifier:
according to guideline
Guideline:
ASTM D93 (Standard test methods for flash point by pensky-martens closed cup tester)
Deviations:
no
GLP compliance:
no
Type of method:
closed cup
Flash point apparatus:
Pensky-Martens apparatus
Key result
Flash point:
66 °C
Atm. press.:
1 016 hPa
Interpretation of results:
GHS criteria not met
Conclusions:
The Flash Point was reported as 66°C at 1,016 hPa.
Executive summary:

The Flash Point for Trans-hex-2-en-1-ol was determined according to the ASTM D93 Standard test methods for flash point by pensky-martens closed cup tester. The Flash Point was reported as 66°C at 1,016 hPa. The substance does not meet the criteria for classification as flammable in accordance with Regulation (EC) No.1272/2008.

Description of key information

The Flash Point for Trans-hex-2-en-1-ol was determined according to the ASTM D93 Standard test methods for flash point by pensky-martens closed cup tester. The Flash Point was reported as 66°C at 1,016 hPa. The substance does not meet the criteria for classification as flammable in accordance with Regulation (EC) No.1272/2008.

Key value for chemical safety assessment

Flash point at 101 325 Pa:
66 °C

Additional information