Registration Dossier

Diss Factsheets

Physical & Chemical properties

Flash point

Currently viewing:

Administrative data

Link to relevant study record(s)

Reference
Endpoint:
flash point of flammable liquids
Type of information:
experimental study
Adequacy of study:
key study
Reliability:
2 (reliable with restrictions)
Rationale for reliability incl. deficiencies:
guideline study with acceptable restrictions
Qualifier:
according to guideline
Guideline:
ASTM D3278 (Standard test methods for flash point of liquids by small scale closed-cup apparatus)
GLP compliance:
no
Type of method:
closed cup
Flash point apparatus:
Setaflash apparatus
Specific details on test material used for the study:
SOURCE OF TEST MATERIAL
- Source and lot/batch number of test material: R-24630
Flash point:
> 93 °C
Atm. press.:
726.19 mm Hg
Remarks on result:
no flash point according to standard method

No flash was identified at 21, 38, 60, 93 °C

In addition testing was ramped between each specific temperatures at a rate of 5 °F/min and was tested every two degrees with no flash detected.

Conclusions:
MTDID 18990 has no flash point at tested temperatures at 21, 38, 60, 93 °C; ASTM D-3278-96.
Executive summary:

No flash-point could be determined using the small scale closed cup method. The study was conducted in accordance with ASTM D3278 and was not GLP compliant; therefore the study is considered reliable with restrictions.

Description of key information

MTDID 18990 has no flash point at tested temperatures at 21, 38, 60, 93 °C; ASTM D-3278-96.

Key value for chemical safety assessment

Additional information

No flash-point could be determined using the small scale closed cup method. The study was conducted in accordance with ASTM D3278 and was not GLP compliant; therefore the study is considered reliable with restrictions.