Registration Dossier

Administrative data

Endpoint:
flash point of flammable liquids
Type of information:
experimental study
Adequacy of study:
key study
Reliability:
1 (reliable without restriction)
Rationale for reliability incl. deficiencies:
guideline study

Data source

Reference
Reference Type:
study report
Title:
Unnamed
Year:
2020
Report Date:
2020

Materials and methods

Test guideline
Qualifier:
according to
Guideline:
other: ASTM D 6450-16 Standard Test Method for Flash Point by Continuously Closed Cup (CCCFP) Tester
GLP compliance:
no
Other quality assurance:
ISO/IEC 17025 (General requirements for the competence of testing and calibration laboratories)
Type of method:
closed cup
Flash point apparatus:
other: Closed-cup Flash Point Tester: MINIFLASH

Test material

Reference
Name:
Unnamed
Type:
Constituent

Results and discussion

Flash point
Key result
Flash point:
ca. 181 °C
Atm. press.:
ca. 101.3 kPa

Applicant's summary and conclusion

Interpretation of results:
GHS criteria not met
Conclusions:
The testing results is 181℃, can be considered valid based on:
- The flash is detected at a temperature that is higher than 18 °C above the initial temperature,
- The deviation between two independent test results was not more than 2℃.