Registration Dossier

Physical & Chemical properties

Flash point

Currently viewing:

Administrative data

Link to relevant study record(s)

Reference
Endpoint:
flash point
Type of information:
experimental study
Adequacy of study:
key study
Study period:
22 July 2010
Reliability:
1 (reliable without restriction)
Rationale for reliability incl. deficiencies:
test procedure in accordance with generally accepted scientific standards and described in sufficient detail
Qualifier:
no guideline followed
Principles of method if other than guideline:
Flash point measured using a manual Pensky Martens Closed Cup apparatus. The sample was heated to 150 ºC, and an ignition source was introduced. The sample was then heated slowly, with the ignition source re-introduced at 10 ºC intervals, until a flash point was observed.
GLP compliance:
no
Type of method:
closed cup
Key result
Flash point:
> 210 - <= 220 °C
Atm. press.:
ca. 101 325 Pa
Interpretation of results:
GHS criteria not met
Conclusions:
The flash point of the substance was measured to be at 210-220 °C
Executive summary:

The flash point of the substance was measured to be at 210-220 °C

Description of key information

The flash point of the substance was measured to be at 210-220 °C

Key value for chemical safety assessment

Flash point at 101 325 Pa:
220 °C

Additional information