Endpoint:
flammable liquids: obsolete as covered by section 'Flash point'
Data waiving:
study scientifically not necessary / other information available
Justification for data waiving:
the study does not need to be conducted because the substance is a liquid
Cross-referenceopen allclose all
Reason / purpose for cross-reference:
data waiving: supporting information
Reference
Endpoint:
flash point of flammable liquids
Type of information:
experimental study
Adequacy of study:
key study
Reliability:
1 (reliable without restriction)
Rationale for reliability incl. deficiencies:
guideline study
Qualifier:
according to guideline
Guideline:
EU Method A.9 (Flash-Point)
Deviations:
no
GLP compliance:
yes (incl. QA statement)
Type of method:
closed cup
Flash point apparatus:
Pensky-Martens apparatus
Specific details on test material used for the study:
SOURCE OF TEST MATERIAL
- Source and lot/batch No.of test material: 41-4205-7137-8, CPDC lot 6
- Expiration date of the lot/batch: 04 Oct 2019
- Purity test date: 99.2%

STABILITY AND STORAGE CONDITIONS OF TEST MATERIAL
- Storage condition of test material: Stored at room temperature
- Stability under test conditions: Stable
Key result
Flash point:
135.3 °C
Atm. press.:
101.1 kPa
Remarks on result:
other:
Remarks:
Average of two runs.
Interpretation of results:
GHS criteria not met
Conclusions:
MTDID 44430 has a flash point of 135.3 °C at 101.1 kPa, determined with a closed-cup testing apparatus according to EC A.9 method.
Executive summary:

MTDID flash point was determined using the Pensky-Martens closed cup method. The study was conducted in accordance with a guideline study under GLP, therefore the study is considered reliable without restrictions and is suitable for Rish Assessment and Classification & Labeling.

Reason / purpose for cross-reference:
data waiving: supporting information
Reference
Endpoint:
auto-ignition temperature (liquids)
Type of information:
experimental study
Adequacy of study:
key study
Study period:
04 Jun 2019 - 05 Jun 2019
Reliability:
1 (reliable without restriction)
Rationale for reliability incl. deficiencies:
guideline study
Qualifier:
according to guideline
Guideline:
ASTM E659 (Standard test method for autoignition temperature of liquid chemicals)
Deviations:
no
GLP compliance:
no
Other quality assurance:
ISO/IEC 17025 (General requirements for the competence of testing and calibration laboratories)
Specific details on test material used for the study:
SOURCE OF TEST MATERIAL
- Source and lot/batch No.of test material: 41-4205-7137-8 CPDC lot #6
Key result
Auto-ignition temperature:
241 - 244 °C
Atm. press.:
754 - 760 mm Hg

Inside Air Temp (°C)

Amount of Sample (ml)

Time (min:sec)

Temp. of Flask Wall (°C) - Top Temp. of Flask Wall (°C) - Side  Temp. of Flask Wall (°C) - Bottom Results / Obervations
 352  0.2  00:01  344  356  356 Small flame, top of flask
 294  0.2  00:01  287  296  297 Small flame inside flask
 274  0.2  00:01  268  274  276 Small flame inside flask
 244  0.2  00:40  239  246  247 Medium flame, top of flask
 209  0.2  10:00  206  212  212 No Ignitoin
 226  0.2  10:00  222  228  229 No Ignitoin
 236  0.2  10:00  232  238  239  No Ignition
 233  0.2  10:00  228  236  233  No Ignition
 240  0.2  10:00  236  243  246  No Ignition
 241  0.2  10:00  238  246  247  No Ignition
 241  0.2  10:00  241  249  249  No Ignition
 241  0.2  10:00  238  246  247  No Ignition
 241  0.3  10:00  241  247  246  No Ignition
 241  0.4  10:00  238  245  246  No Ignition
 241  0.5  10:00  240  245  246  No Ignition
 241  0.1  10:00  240  245  246  No Ignition
 241  0.05  10:00  240  245  245  No Ignition
Conclusions:
The autoignition temperature of MTDID 44430 was determined to be between 241 °C and 244 °C (ASTM E-659).
Executive summary:

MTDID 44430 was determined to have an autoignition temperature of 241 and 244 °C, measured at atmospheric pressure of 754 mmHg and 760 mmHg. The study was conducted in accordance with ASTM E-659 and was ISO 17025 compliant; therefore the study is considered reliable without restrictions.

Data source

Materials and methods

Results and discussion